Product Name : G7TUPS500Item# : 114555-184
Model : 114555-184
Was Price: CNY0/pcNow Price : CNY0/pcLast update : 2017.10.26
Manufacturer :

MGE Galaxy 7000 500 kVA
A high-adaptability, 3-phase UPS that meets the unique requirements of medium to large data centers, industry, buildings, and mission-critical environments. This UPS includes ECO Mode, with cost-saving energy efficiency, and SPoT operation mode, which increases on-site test capability without additional load bank.
Includes: Installation guide , Network Management Card , User Manual
G7TUPS500Features
MGE Galaxy 7000 500 kVA
-
Audible alarms
Provides notification of changing utility power and UPS power conditions
-
Generator compatible
Ensures clean, uninterrupted power to protected equipment when generator power is used.
-
Manual maintenance bypass
Reduces installation costs by eliminating the need for an external mechanical bypass.
Galaxy 7000Features & Benefits
Compatibility
-
Parallel capability
Multiple units can be placed in parallel to meet power capacity and redundancy requirements
-
Output synchronization to external source
UPS systems can be synchronized with any other independent source for use with downstream static transfer switches.
-
Compatible with Schneider Electric's lithium ion battery solution
Reduces system footprint and weight, cooling and maintenance requirements, and total cost of ownership; offers double the life of VRLA batteries; and improves backup storage predictablity and manageability.
Economy
-
Advanced electrical features
Excellent power conditioning, very low harmonic distortion through IGBT rectifier, input power factor correction, and high power efficiency
-
ECO Mode
Operating mode that by-passes unused electrical components in good power conditions to achieve high operating efficiency without sacrificing protection
-
Fully-rated power kVA equals kW
Reduces cost by eliminating the need for an oversized UPS for Power Factor Corrected (PFC) loads.
Manageability
-
Network management capability
Full-featured network management interfaces that provide standards-based management via Web, SNMP, and Telnet.
Sustainability
Availability
-
High availability architecture
Different running modes : hot stand-by, integrated parallel, or centralized static switch for multi-modules leading to availability architectures
Output
-
Output power capacity
450.0 KWatts / 500.0 kVA
-
Max Configurable Power (Watts)
450.0 KWatts / 500.0 kVA
-
Nominal Output Voltage
400V 3PH
-
Neutral Output Current
938A
-
Output Voltage Note
Configurable for 380 : 400 or 415 V 3 Phase nominal output voltage
-
Output Voltage Distortion
Less than 2%
-
Output Frequency (sync to mains)
50 Hz, 60 Hz
-
Output Frequency (not synced)
60Hz +/- 0.1% for 60Hz nominal, 50Hz +/- 0.1% for 50Hz nominal
-
Other Output Voltages
380, 415, 440
-
Load Crest Factor
2.5 : 1
-
Topology
Double Conversion Online
-
Waveform type
Sine wave
-
Maximum Output Current
2369
-
Output Connections
(1) Hard Wire 4-wire (3PH + N) (Battery Backup)
(1) Hard Wire 3-wire (3PH) (Battery Backup)
(1) Hard Wire 4-wire (3PH - PEN) (Battery Backup)
(1) Hard Wire 4-wire (3PH + G) (Battery Backup)
(1) Hard Wire 5-wire (3PH + N + G) (Battery Backup)
-
Output Voltage THD
< 2% linear load and <3% non-linear load
-
Bypass
Built-in Maintenance Bypass
Input
-
Nominal Input Voltage
400V 3PH
-
Input frequency
45 - 65 Hz
-
Input Connections
Hard Wire 5-wire (3PH + N + G)
-
Input voltage range for main operations
340 - 460 (400V)V
-
Input Total Harmonic Distortion
Less than 3% for full load
-
Type of Input Protection Required
3-pole breaker
-
Other Input Voltages
380, 415, 450
-
Maximum Short Circuit Withstand (Icw)
200.0kAmps
-
Maximum Input Current
735.0A
-
Input Power Factor at Full Load
1.0
Batteries & Runtime
-
Battery type
VRLA
-
Efficiency
Communications & Management
-
Pre-Installed SmartSlot™ Cards
AP9635CH
-
Control panel
Multi-function LCD status and control console
-
Audible Alarm
Audible and visible alarms prioritized by severity
-
Emergency Power Off (EPO)
Yes
-
Available SmartSlot™ Interface Quantity
1
Physical
Environmental
-
Operating Environment
0 - 35 °C
-
Operating Relative Humidity
20 - 80 %
-
Operating Elevation
0-999.9meters
-
Storage Temperature
-25 - 40 °C
-
Storage Relative Humidity
20 - 80 %
-
Storage Elevation
0-9000meters
-
Audible noise at 1 meter from surface of unit
72.0dBA
-
Protection Class
IP 20
Conformance
-
Approvals
CE, EN 60950, EN/IEC 62040-2, EN/IEC 62040-3, ISO 14001, ISO 9001, LCIE, VFI-SS-111
-
Standard warranty
1 year repair or replace
Sustainable Offer Status
-
Battery Directive
Compliant
-
Battery Notes
ts_Battery_Notes
General
-
Bypass Connection
4 wire (3Ph + N) or 5 wire (3Ph + N + G)
-
Bypass Protection Device
800.0
-
Max Bypass Input Current
844.0A