Product Name : ACRC103Item# : 202623-175
Model : 202623-175
Was Price: CNY0/pcNow Price : CNY0/pcLast update : 2016.12.31
Manufacturer :

InRow Chilled Water Cooling
In Row RC Chilled Water, 200-240V 50/60 Hz, IEC 309-16
Close-coupled, chilled water cooling for medium to large data centers
Includes: Installation guide, Operations and maintenance manual
Hot swappable fans
Allows system to remain operational if a fan replacement is required.
Washable filters
Easy to maintain, cleanable, deep loading mesh filter removes particles from the return air stream.
InRow Chilled Water Cooling Features & Benefits
Predictable cooling
Placing the unit in the row of racks moves the source of cooling closer to the heat load. This eliminates air mixing and provides a predictable cooling architecture.
Dual A-B Power Inputs
Draws power from the UPS for power protection with dual feeds for redundancy.
Rack inlet control
Rack inlet control guarantees inlet temperature to IT equipment.
Top and bottom chilled water connections
Allows chilled water to be connected from the top, if routing from overhead, or bottom, if on a raised floor.
Active response controls
Monitors and actively adjusts cooling capacity to ensure proper server inlet temperatures. Through the microprocessor controller, visibility into the operation and health of the unit is provided.
Variable speed fans
Variable speed fans reduce energy consumption during off-peak cooling periods.
Row-based architecture
Captures hot exhaust air directly from the IT equipment, thereby increasing the unit's sensible cooling capacity over traditional cooling architectures.
Modular design
Modular design provides scalable solutions to add cooling as demand increases.
Scaleable densities
Allows for higher densities to be achieved by integrating containment with room, row and rack cooling system architectures.
Casters
Provides flexibility to move the unit to wherever cooling is required.
Easy service access
Allows for all serviceable components to be replaced/maintained by easily accessible panels/doors.
Real-Time Capacity Monitoring
Real-time display of current and available cooling.
Microprocessor controller
Provides proactive control and real-time monitoring via a four line, eighty character, alphanumeric display.
Building management system integration
Send alarms and data points allowing you to manage critical building infrastructure from a single system.
Cooling Type
Chilled Water
Nominal Cooling Capacity
18.20 kW
Entering Coolant Temperature
45.0 °F (7.22 °C)
Entering Air Relative Humidity
32.0%
Entering Air Temperature
85.0 °F (29.44 °C)
Coolant pressure drop
7.33 psi (50.56 kpa)
Coolant flow rate
13.16 gpm (0.83 lps)
Based on sea level operation
Air Discharge Patterns
Horizontal
Air Flow
2900.0 CFM (1368.64 lps)
Minimum Water Inlet Temperature
45.0 °F (7.00 °C)
Condensate Pump Capacity
1.300 gal/hour (0.002 lps)
Communications & Management
Control panel
Multi-function LCD status and control console
Audible Alarm
Audible and visible alarms prioritized by severity
Interface Port(s)
Input contact closure
Maximum Height
78.39 inches (1991 mm)
Maximum Width
11.80 inches (300 mm)
Maximum Depth
42.13 inches (1070 mm)
Net Weight
358.00 lbs. (162.73 kg)
Shipping Weight
425.50 lbs. (193.41 kg)
Shipping Height
83.39 inches (2118 mm)
Shipping Width
29.38 inches (746 mm)
Shipping Depth
44.75 inches (1137 mm)
Regulatory Approvals
C-tick, CE, EN 55022 Class A, EN 55024, EN 60950, GOST, IEC 60950, IEC 61000-3-2, IEC 61000-3-3, MEA, VDE
Standard Warranty
1 year (parts only), 1 year on-site repair or replace with factory authorized Start-Up