TEL:021-3152 3588    Join Now   Sign In   Cart -  中文
Product Name : SYMF1600KH
Item# : 1792-410
Model : 1792-410
Was Price: CNY0/pc
Now Price : CNY0/pc
Last update : 2017.10.26
Manufacturer :
More Picture:

Symmetra MW 1600kW Frame, 400V

Includes: Assembly service , Installation Guide , Start-Up Service , User Manual

 

Symmetra MWFeatures & Benefits

Sustainability
  • EU CoC for UPS
    Ensures that UPSs sold in the EU are highly efficient
 
Agility
  • Parallel-redundant capable
    Power the connected equipment with multiple uninterruptible power supplies to increase system redundancy
  • Parallel-capacity capable
    Increases total power capacity by using multiple uninterruptible power supplies simultaneously.
  • Multiple cable-entry points
    Provides flexibility of UPS placement in the room and easy access to install cabling to the terminal blocks.
  • Scalable runtime
    Allows additional run time to be quickly added as needed.
  • Front-access servicing
    Simplifies installation and UPS maintenance while minimizing space requirements.
  • Scalable power capacity
    Reduces UPS over-sizing costs today by allowing quick power upgrades, within the same footprint, later.
 
Total Cost of Ownership
  • Compatible with Schneider Electric's lithium ion battery solution
    Reduces system footprint and weight, cooling and maintenance requirements, and total cost of ownership; offers double the life of VRLA batteries; and improves backup storage predictablity and manageability.
  • Temperature-compensated battery charging
    Prolongs battery life by regulating the charge voltage according to battery temperature.
  • Automatic self-test
    Periodic battery self-test ensures early detection of a battery that needs to be replaced.
  • Intelligent battery management
    Maximizes battery performance, life, and reliability through intelligent, precision charging.
  • Manageable external batteries
    Reduces preventative maintenance service needs by monitoring the health and status of the external batteries and their expected runtime.
  • Fully-rated power kVA equals kW
    Reduces cost by eliminating the need for an oversized UPS for Power Factor Corrected (PFC) loads.
  • Input power factor correction
    Minimizes installation costs by enabling the use of smaller generators and cabling.
 
Availability
  • Generator compatible
    Ensures clean, uninterrupted power to protected equipment when generator power is used.
  • Configurable for N+1 internal redundancy
    Provides high availability through redundancy by allowing configuration with one more Power Module than is necessary to support the connected load.
  • Network manageable
    Provides remote power management of the UPS over the network.
  • Audible alarms
    Provides notification of changing utility power and UPS power conditions
  • Power Modules connected in parallel
    Enhances availability by allowing immediate, seamless recovery from isolated module failures.
  • Modular design
    Provides fast serviceability and reduced maintenance requirements via self-diagnosing, field-replaceable modules.
  • Battery failure notification
    Provides early-warning fault analysis on batteries enabling timely preventive maintenance
 
Marketing Features
  • Scalable power capacity
    Reduces UPS over-sizing costs today by allowing quick power upgrades, within the same footprint, later.
  • Battery modules connected in parallel
    Delivers higher availability through redundant batteries.
  • LCD display
    Provides schematic overview of critical data for guided operation and troubleshooting on color LCD touch-screen.
  • Modular design
    Provides fast serviceability and reduced maintenance requirements via self-diagnosing, field-replaceable modules.
  • Input power factor correction
    Eliminates the need for an external phase-compensation unit and minimizes installation costs by enabling the use of smaller generators and cabling.
  • Fully-rated power kVA equals kW
    Reduces cost by eliminating the need for an oversized UPS for Power Factor Corrected (PFC) loads.
  • Generator compatible
    Ensures clean, uninterrupted power to protected equipment when generator power is used.
  • Power Modules connected in parallel
    Enhances availability by allowing immediate, seamless recovery from isolated module failures.
  • Configurable for N+1 internal redundancy
    Provides high availability through redundancy by allowing configuration with one more Power Module than is necessary to support the connected load.

    Output

    • Output power capacity
      1.6 MWatts / 1.6 MVA
    • Max Configurable Power (Watts)
      1.6 MWatts / 1.6 MVA
    • Nominal Output Voltage
      400V 3PH
    • Output Voltage Note
      Configurable for 380 : 400 or 415 V 3 Phase nominal output voltage
    • Output Voltage Distortion
      Less than 5% at full load
    • Output Frequency (sync to mains)
      50 Hz - programmable +/- 0.5 / 1 / 2 / 4 / 6 / 8%
    • Output Frequency (not synced)
      50Hz +/- 0.1% for 50Hz nominal
    • Other Output Voltages
      380, 415
    • Load Crest Factor
      Unlimited
    • Topology
      Delta Conversion On-Line
    • Waveform type
      Sine wave
    • Maximum Output Current
      2940
    • Output Connections
      (1) Hard Wire 5-wire (3PH + N + G) (Battery Backup)
      (1) Hard Wire 4-wire (3PH + N) (Battery Backup)
      (1) Hard Wire 4-wire (3PH + G) (Battery Backup)
      (1) Hard Wire 4-wire (3PH - PEN) (Battery Backup)
    • Bypass
      External Static Bypass

    Input

    • Nominal Input Voltage
      400V 3PH
    • Input frequency
      50 Hz - programmable +/- 0.5 / 1 / 2 / 4 / 6 / 8%
    • Input Connections
      Hard Wire 4-wire (3PH + G), Hard Wire 4-wire (3PH + PEN), Hard Wire 5-wire (3PH + N + G)
    • Input voltage range for main operations
      323 - 437 (380V), 340 - 460 (400V), 353 - 477 (415V)V
    • Input voltage adjustable range for mains operation
      323 - 437 (380V), 340 - 460 (400V), 357 - 477 (415V)V
    • Number of Power Cords
      1
    • Other Input Voltages
      380, 415
    • Input Power Factor at Full Load
      0.99

    Batteries & Runtime

    • Battery type
      No internal battery - uses external battery system
    • Extendable Run Time
      1
    • Extended Run Options
      Symmetra-MW-1600kW-Frame-400V
    • Efficiency

     

     

    Communications & Management

    • Interface Port(s)
      Contact Closure , DB-9 RS-232 , RJ-45 10/100 Base-T , RS-485 , SYMWSUCBL
    • Control panel
      Touch Screen LCD User Interface
    • Audible Alarm
      Audible and visible alarms prioritized by severity
    • Emergency Power Off (EPO)
      Yes

    Physical

    • Maximum Height
      2032mm , 203.2cm
    • Maximum Width
      5486mm , 548.6cm
    • Maximum Depth
      1067mm , 106.7cm
    • Net Weight
      6376.36kg
    • Shipping weight
      6576.36kg
    • Shipping Height
      2235mm , 223.5cm
    • Shipping Width
      6240mm , 624.0cm
    • Shipping Depth
      1280mm , 128.0cm
    • Color
      Light grey (NCS 2703-G84Y)
    • Units per Pallet
      1.0

    Environmental

    • Operating Environment
      0 - 40 °C
    • Operating Relative Humidity
      0 - 95 %
    • Operating Elevation
      0-999.9meters
    • Storage Temperature
      -50 - 40 °C
    • Storage Relative Humidity
      0 - 95 %
    • Storage Elevation
      0-15000meters
    • Audible noise at 1 meter from surface of unit
      75.0dBA
    • Online thermal dissipation
      168960.0BTU/hr
    • Protection Class
      IP 20

    Conformance

    • Approvals
      CE, EN 50091-1, EN 50091-2, EN 50091-3, EN 60950, EN/IEC 62040-3, FCC Part 15 Class A, IEC 60950, ISO 14001, ISO 9001, VFI-SS-111
    • Standard warranty
      1 year repair or replace

 